Pelican Wireless · Thermostat

Pelican Wireless TC4 Commercial Thermostat with Humidity and CO₂

Connected commercial thermostat with temperature, humidity and CO₂ sensing for Pelican building controls. Requires a Pelican Gateway.

Pelican Wireless TC4

Pelican Wireless TC4

Will this work with my system?

Match your equipment to these requirements before ordering.

Works with

  • 24 V AC conventional and heat-pump systems; two-/four-pipe fan coils per wiring guide; zoning requires the separate Pelican zoning design
  • Staging: Conventional: up to 2 heating / 2 cooling stages; heat pump: up to 2 compressor stages plus auxiliary/emergency heat. Two-speed fan configurations reduce available stage outputs.

System requirements

  • Supply voltage: 24 V AC nominal, 60 Hz; operating range 23–30 V AC
  • Power: Hardwired AC
  • Wiring: Configuration-dependent: direct wiring uses R/C; included wiring module supports a minimum three-wire R/C/D link. Not a wire-free or battery-powered installation.
  • Electrical load limits: 2.0 A running on Y, Y2, W, W2 and G; TC4 Hu/Dh: 1.0 A running
  • Connection: Pelican mesh network; not Wi-Fi

Limitations & exclusions

  • Not a battery-powered or wire-free thermostat; hardwired power is required.

Check before you buy

  1. Match the equipment type, stages and fan speeds to the exact TC-model wiring diagram; two-speed fan configurations reduce available stage outputs.
  2. Confirm a Pelican gateway and mesh connection for configuration and remote management.
  3. Check the R/C wiring or the included module’s minimum three-wire R/C/D connection against the installation guide.
Installation & configuration details
  • PEARL and TA1 are optional accessories with application-specific wiring and configuration. A TC thermostat supports one PEARL and one TA1.
  • PEARL demand-based ventilation requires a CO2-sensing TC3 or TC4 and appropriate connected equipment.
Manufacturer documentation (2)

Use these documents to compare your exact model and configuration.

Overview

Part of the Pelican Wireless system. See the system overview for component roles and selection requirements.

The TC4 is a touchscreen thermostat for commercial spaces using Pelican building controls. It combines local temperature adjustment with centrally managed schedules and operating information through the Pelican web application. TC4 adds built-in relative-humidity and carbon-dioxide sensing, with dedicated humidification and dehumidification outputs for suitable equipment.

Equipment and system requirements

A Pelican Gateway is required to configure and manage this thermostat. Its radio communicates over Pelican’s mesh network rather than directly over Wi-Fi. Check the building’s gateway and network arrangement before selecting this product.

The installation guide covers conventional equipment, heat pumps and two- or four-pipe fan coils. Output assignments change with the equipment and fan configuration; the guide must be checked against the actual system. Pelican zone-damper applications use additional system components and their separate installation guide.

Occupant controls and scheduling

The touch interface supports local adjustment subject to administrator restrictions. The system provides daily, weekday/weekend and seven-day scheduling, temporary schedule overrides, vacation operation, keypad lockout and adjustable heat/cool setpoint limits.

Installation considerations

This is a hardwired 24 V AC device. The supplied limited-wiring module can be used where the equipment-to-thermostat connection has at least three suitable conductors. It does not eliminate the need for power and a common connection at the installed components. Use the model-specific manual for wiring and siting.

Technical document notes

Pelican’s current series data sheet and product page disagree on dimensions and the lower ambient operating limit. Those values are intentionally omitted here pending confirmation of the applicable hardware revision. The CO₂ calibration certificate also includes an accuracy qualifier that is absent from the shorter data-sheet statement; consult the certificate before using the reading for a specified accuracy requirement.

Product details

Manufacturer
Pelican Wireless
SKU
190135
Model / MPN
TC4
Condition
New
Lifecycle
Current

Specifications

Power sources
Hardwired AC
Supply voltage
24 V AC nominal, 60 Hz; operating range 23–30 V AC
Communication protocols
Pelican mesh network; not Wi-Fi
Wireless standards
IEEE 802.15.4
Radio bands
2.4 GHz
Operating humidity
5–90% RH, non-condensing
Storage temperature
−20°F to 160°F
Remote management
Pelican web application through a Pelican Gateway
Supply current
105 mA at 24 V AC, 60 Hz
Control functions
Temperature; humidity
Equipment types
24 V AC conventional and heat-pump systems; two-/four-pipe fan coils per wiring guide; zoning requires the separate Pelican zoning design
Stage modes
Conventional: up to 2 heating / 2 cooling stages; heat pump: up to 2 compressor stages plus auxiliary/emergency heat. Two-speed fan configurations reduce available stage outputs.
Control signal types
Switched 24 V AC HVAC outputs; follow model-specific terminal diagrams
Scheduling modes
Daily, 5-2 and 7-day scheduling through the Pelican web application
Schedule periods per day
Up to 12 scheduled set times per day; maximum only, not a verified list of selectable counts
Keypad lockout
Administrator-managed and schedulable lockout; exact selectable levels not established
Setpoint limits
Administrator can limit heating and cooling setpoint adjustment; exact configurable bounds not established
System modes
Auto, Heat, Cool and Off; selectable modes depend on configuration
Local controls
Touchscreen
Hold options
Temporary schedule override and vacation mode; durations depend on configuration
Mounting methods
Interior wall or vertical single-gang electrical box; avoid metal surfaces/enclosures
C wire requirement
Configuration-dependent: direct wiring uses R/C; included wiring module supports a minimum three-wire R/C/D link. Not a wire-free or battery-powered installation.
Measured variables
Temperature, relative humidity, carbon dioxide
Measurement channels
CO₂ detection range: 400–2000 ppm; accuracy omitted pending reconciliation of calibration certificate and datasheet
Contact ratings
2.0 A running on Y, Y2, W, W2 and G; TC4 Hu/Dh: 1.0 A running
Fan modes
Auto and On; High/Low selections depend on equipment configuration
Humidity control modes
Humidification and dehumidification via dedicated Hu/Dh outputs with appropriate external equipment; not merely humidity display

Documents & downloads

Optional components

Pelican Wireless PEARL

Pelican Wireless

Pelican Wireless PEARL Advanced Equipment Controller

Model PEARL SKU 190108

Pelican thermostat accessory for economizer, ventilation, variable-speed fan and modulating equipment control.

Supply voltage
24 V AC, 60 Hz
Communication protocols
Three-wire connection to a Pelican thermostat
Power sources
Hardwired AC

Loading price…

View details
Pelican Wireless TA1

Pelican Wireless

Pelican Wireless TA1 Temperature and Alarm Sensor

Model TA1 SKU 190104

Wired sensor accessory for temperature monitoring, averaging, or a dry-contact input on a compatible Pelican device.

Communication protocols
Pelican three-wire R/C/D connection
Mounting
Flat surface in a moisture-free location; device is not waterproof
Power sources
Hardwired AC