Pelican Wireless · Thermostat
Pelican Wireless TC2 Commercial Thermostat with Humidity
Connected commercial thermostat with temperature and humidity sensing plus dedicated humidity-control outputs.
Will this work with my system?
Match your equipment to these requirements before ordering.
Works with
- 24 V AC conventional and heat-pump systems; two-/four-pipe fan coils per wiring guide; zoning requires the separate Pelican zoning design
- Staging: Conventional: up to 2 heating / 2 cooling stages; heat pump: up to 2 compressor stages plus auxiliary/emergency heat. Two-speed fan configurations reduce available stage outputs.
System requirements
- Supply voltage: 24 V AC nominal, 60 Hz; operating range 23–30 V AC
- Power: Hardwired AC
- Wiring: Configuration-dependent: direct wiring uses R/C; included wiring module supports a minimum three-wire R/C/D link. Not a wire-free or battery-powered installation.
- Electrical load limits: 2.0 A running on Y, Y2, W, W2 and G; TC2 Hu/Dh: 1.0 A running
- Connection: Pelican mesh network; not Wi-Fi
Limitations & exclusions
- Not a battery-powered or wire-free thermostat; hardwired power is required.
Check before you buy
- Match the equipment type, stages and fan speeds to the exact TC-model wiring diagram; two-speed fan configurations reduce available stage outputs.
- Confirm a Pelican gateway and mesh connection for configuration and remote management.
- Check the R/C wiring or the included module’s minimum three-wire R/C/D connection against the installation guide.
Installation & configuration details
- PEARL and TA1 are optional accessories with application-specific wiring and configuration. A TC thermostat supports one PEARL and one TA1.
- PEARL demand-based ventilation requires a CO2-sensing TC3 or TC4 and appropriate connected equipment.
Manufacturer documentation (2)
Use these documents to compare your exact model and configuration.
Overview
Part of the Pelican Wireless system. See the system overview for component roles and selection requirements.
TC2 is a Pelican touchscreen thermostat with built-in temperature and relative-humidity sensing. Dedicated humidification and dehumidification outputs operate appropriate external equipment; the TC2 does not include the CO₂ sensor found in TC3 and TC4.
Equipment and system requirements
A Pelican Gateway and mesh connection are required for configuration and remote management. The installation guide covers conventional equipment, heat pumps and two- or four-pipe fan coils. Output assignments depend on the equipment and fan-speed configuration. Zoning applications require their separate system design.
Occupant controls and scheduling
The touch interface provides local adjustment subject to administrator controls. Pelican scheduling supports daily, weekday/weekend and seven-day arrangements, temporary overrides, keypad restrictions and heating/cooling setpoint limits.
Installation considerations
TC2 requires hardwired 24 V AC power. The included limited-wiring module supports an R/C/D connection where at least three suitable conductors are available; it is not a battery-powered or wire-free installation.
Technical document notes
The manufacturer's product page and series datasheet disagree on enclosure dimensions and the lower ambient operating limit. Those optional figures are withheld pending hardware-revision confirmation.
Product details
- Manufacturer
- Pelican Wireless
- SKU
- 190133
- Model / MPN
- TC2
- Condition
- New
- Lifecycle
- Current
Specifications
- Power sources
- Hardwired AC
- Supply voltage
- 24 V AC nominal, 60 Hz; operating range 23–30 V AC
- Communication protocols
- Pelican mesh network; not Wi-Fi
- Wireless standards
- IEEE 802.15.4
- Radio bands
- 2.4 GHz
- Operating humidity
- 5–90% RH, non-condensing
- Storage temperature
- −20°F to 160°F
- Remote management
- Pelican web application through a Pelican Gateway
- Supply current
- 105 mA at 24 V AC, 60 Hz
- Control functions
- Temperature; humidity
- Equipment types
- 24 V AC conventional and heat-pump systems; two-/four-pipe fan coils per wiring guide; zoning requires the separate Pelican zoning design
- Stage modes
- Conventional: up to 2 heating / 2 cooling stages; heat pump: up to 2 compressor stages plus auxiliary/emergency heat. Two-speed fan configurations reduce available stage outputs.
- Control signal types
- Switched 24 V AC HVAC outputs; follow model-specific terminal diagrams
- Scheduling modes
- Daily, 5-2 and 7-day scheduling through the Pelican web application
- Schedule periods per day
- Up to 12 scheduled set times per day; maximum only, not a verified list of selectable counts
- Keypad lockout
- Administrator-managed and schedulable lockout; exact selectable levels not established
- Setpoint limits
- Administrator can limit heating and cooling setpoint adjustment; exact configurable bounds not established
- System modes
- Auto, Heat, Cool and Off; selectable modes depend on configuration
- Local controls
- Touchscreen
- Hold options
- Temporary schedule override and vacation mode; durations depend on configuration
- Mounting methods
- Interior wall or vertical single-gang electrical box; avoid metal surfaces/enclosures
- C wire requirement
- Configuration-dependent: direct wiring uses R/C; included wiring module supports a minimum three-wire R/C/D link. Not a wire-free or battery-powered installation.
- Measured variables
- Temperature and relative humidity
- Contact ratings
- 2.0 A running on Y, Y2, W, W2 and G; TC2 Hu/Dh: 1.0 A running
- Fan modes
- Auto and On; High/Low selections depend on equipment configuration
- Humidity control modes
- Humidification and dehumidification via dedicated Hu/Dh outputs with appropriate external equipment; not merely humidity display
Documents & downloads
- Installation guide (PDF)
TC2 Installation Guide (PDF)
- Specification sheet (PDF)
TC Series Datasheet — see technical document notes (PDF)
- Installation guide (PDF)
Zone Damper Installation Guide — system reference (PDF)
- Wireless Network and Installation Planning Guide — system reference (PDF) (PDF)
- Section 23 09 22: Climate Management Controls for HVAC — system reference (PDF) (PDF)
- Network Security — system reference (PDF) (PDF)
- Wireless Communication Frequency — system reference (PDF) (PDF)
- Warranty (PDF)
Warranty — system reference (PDF)
Optional components

Pelican Wireless
Pelican Wireless PEARL Advanced Equipment Controller
Model PEARL SKU 190108
Pelican thermostat accessory for economizer, ventilation, variable-speed fan and modulating equipment control.
- Supply voltage
- 24 V AC, 60 Hz
- Communication protocols
- Three-wire connection to a Pelican thermostat
- Power sources
- Hardwired AC
Price: $203.07
View details
Pelican Wireless
Pelican Wireless TA1 Temperature and Alarm Sensor
Model TA1 SKU 190104
Wired sensor accessory for temperature monitoring, averaging, or a dry-contact input on a compatible Pelican device.
- Communication protocols
- Pelican three-wire R/C/D connection
- Mounting
- Flat surface in a moisture-free location; device is not waterproof
- Power sources
- Hardwired AC