Product selection

Compare products

Review up to four products side by side. Copy this page’s URL to share your selection.

Add another product from the catalog for a side-by-side comparison.

Compare documented specifications below. “Not specified” means the catalog has no value; it does not mean a feature or requirement is absent. Confirm system compatibility before choosing a replacement. On smaller screens, scroll the table horizontally.

Product specifications and system requirements
SpecificationPelican Wireless TC2 Commercial Thermostat with Humidity
BrandPelican Wireless
ModelTC2
SKU190133
Component roleThermostat
LifecycleCurrent
Building systems
RequiresNot specified
C wire requirementConfiguration-dependent: direct wiring uses R/C; included wiring module supports a minimum three-wire R/C/D link. Not a wire-free or battery-powered installation.
Communication protocolsPelican mesh network; not Wi-Fi
Contact ratings2.0 A running on Y, Y2, W, W2 and G; TC2 Hu/Dh: 1.0 A running
Control functionsTemperature; humidity
Control signal typesSwitched 24 V AC HVAC outputs; follow model-specific terminal diagrams
Equipment types24 V AC conventional and heat-pump systems; two-/four-pipe fan coils per wiring guide; zoning requires the separate Pelican zoning design
Fan modesAuto and On; High/Low selections depend on equipment configuration
Heating and cooling stagesConventional: up to 2 heating / 2 cooling stages; heat pump: up to 2 compressor stages plus auxiliary/emergency heat. Two-speed fan configurations reduce available stage outputs.
Hold optionsTemporary schedule override and vacation mode; durations depend on configuration
Humidity control modesHumidification and dehumidification via dedicated Hu/Dh outputs with appropriate external equipment; not merely humidity display
Keypad lockoutAdministrator-managed and schedulable lockout; exact selectable levels not established
Local controlsTouchscreen
Measured variablesTemperature and relative humidity
MountingInterior wall or vertical single-gang electrical box; avoid metal surfaces/enclosures
Operating humidity5–90% RH, non-condensing
Power sourcesHardwired AC
Radio bands2.4 GHz
Remote managementPelican web application through a Pelican Gateway
Schedule periods per dayUp to 12 scheduled set times per day; maximum only, not a verified list of selectable counts
SchedulingDaily, 5-2 and 7-day scheduling through the Pelican web application
Setpoint limitsAdministrator can limit heating and cooling setpoint adjustment; exact configurable bounds not established
Storage temperature−20°F to 160°F
Supply current105 mA at 24 V AC, 60 Hz
Supply voltage24 V AC nominal, 60 Hz; operating range 23–30 V AC
System modesAuto, Heat, Cool and Off; selectable modes depend on configuration
Wireless standardsIEEE 802.15.4