SpecificationHoneywell T7350M1008 Commercial Modulating Thermostat
BrandHoneywell
ModelT7350M1008
SKU365051
Component roleStandalone
LifecycleDiscontinued
Building systemsNot specified
RequiresNot specified
Contact ratingsRelay outputs: 1.5 A running maximum and 7.5 A inrush maximum at 30 VAC
Control signal typesTwo 4–20 mA modulating outputs; 510 ohm maximum terminating resistance
Dual transformer supportDocumented for T7350M; follow installation Figure 12 and jumper requirements
Heating and cooling stagesT7350M: two modulating outputs plus two relay outputs; auxiliary relay can add one heat or cool stage, subject to configuration
Keypad lockoutTwo lockout levels in addition to unlocked; special keypress functions are not locked out
Operating humidity5–90% RH, noncondensing
Operating temperature30–110 °F (-1–43 °C)
Power consumption5 VA maximum without load at 30 VAC, 50/60 Hz
Power sourcesHardwired AC; no batteries required
Remote sensor supportOptional room, outdoor, discharge-air and humidity inputs; select sensors from the T7350 accessory list
Schedule periods per dayTwo occupied and two not-occupied periods per day
Scheduling7-day occupied / not-occupied schedule
Setpoint limitsOccupied setpoints are constrained by configured stops, not-occupied setpoints and the heating/cooling deadband; see product data p.17
Setpoint rangeHeating 40–90 °F (4–32 °C); cooling 45–99 °F (7–37 °C)
Supply voltage24 VAC nominal (20–30 VAC), 50/60 Hz