| Specification | C7100A1015 Averaging Duct Temperature Sensor |
|---|---|
| Brand | Honeywell |
| Model | C7100A1015 |
| SKU | 361983 |
| Component role | Sensor |
| Lifecycle | Current |
| Building systems | Not specified |
| Requires | Not specified |
| Calibration method | No settings or field calibration required |
| Control sequence | Averaging discharge-air temperature sensing |
| Electrical connections | Two recessed 1/4 in. quick-connect terminals |
| Measured variables | Temperature |
| Mounting | Duct or plenum flange; 2 × 4 in. junction box |
| Operating temperature | 40–220°F (4–104°C) |
| Sensor characteristic | PT3000 platinum thick-film; 3484 ohms nominal at 77°F (25°C) |
| Sensor output types | Resistance |