Johnson Controls · Equipment controller

Johnson Controls W43A-14C Room Humidistat

SPDT room humidistat with a 0–70% RH setpoint range for humidifying or dehumidifying control.

Johnson Controls W43A-14C

Johnson Controls W43A-14C

Will this work with my system?

Match your equipment to these requirements before ordering.

System requirements

  • Electrical load limits: Full load: 6 A at 120 V AC; 3.5 A at 208 V AC; 3 A at 240 V AC. Locked rotor: 36 A at 120 V AC; 21 A at 208 V AC; 18 A at 240 V AC. Pilot duty: 125 VA at 24/277 V AC.
  • Sensor input: Human-hair humidity sensing element

Check before you buy

  1. Match the full W43A-14C model number and hardware revision to the manufacturer's equipment manual and accessory list.
  2. Compare the equipment terminals, control voltage and required operating sequence with the model-specific installation diagrams.
Manufacturer documentation (1)

Use these documents to compare your exact model and configuration.

The W43A-14C switches humidifying or dehumidifying equipment according to room relative humidity. Its mechanical sensing element operates snap-action SPDT contacts, with an approximately 6% RH fixed differential.

The unit includes a vertical faceplate and an additional horizontal faceplate. Adjustable upper and lower stops restrict the setting range or lock the dial. Mount it on a 2 x 4 in. wall box in a representative location, following the technical bulletin.

This is an operating humidity control. Where failure could cause injury or property loss, the manufacturer requires appropriate independent protective controls or warning systems.

Product details

Manufacturer
Johnson Controls
SKU
577240
Model / MPN
W43A-14C
Condition
New
Lifecycle
Current

Specifications

Mounting methods
Vertical or horizontal 2 x 4 in. wall box
Dimensions
4.71 x 2.96 x 2.94 in. (H x W x D)
Setpoint limits
Adjustable high and low stops; dial lock possible
Contact ratings
Full load: 6 A at 120 V AC; 3.5 A at 208 V AC; 3 A at 240 V AC. Locked rotor: 36 A at 120 V AC; 21 A at 208 V AC; 18 A at 240 V AC. Pilot duty: 125 VA at 24/277 V AC.
Humidity control modes
Humidification or dehumidification; 0–70% RH setpoint range
Control sequence
SPDT snap-action switching; fixed differential approximately 6% RH
Sensor characteristic
Human-hair humidity sensing element
Switch configuration
SPDT

Documents & downloads